Position: Home > Solution & Case > Solutions > Detalles

Telecom Bureau station UPS battery monitoring program

: 2017-09-01 02:32:43 | : 1123

Communication Bureau station UPS battery monitoring program

 Lead-acid battery is a battery backup power supply 110V/220V power the most commonly used. Frequency of lead-acid batteries currently running network capacity deterioration, lack of spare time phenomenon is higher, resulting in part of the actual battery life is much lower than the design life. Unstable power system battery performance is particularly UPS power system, a huge risk of stability.

 

    By introducing the line battery monitoring and management system, in order to achieve real-time monitoring for batteries and effective maintenance purposes. The main role is to:


1, to protect each single battery charge rationality voltage, current and temperature operating parameters.
2, for each single battery by AC impedance (non-DC resistance) online test to accurately determine the deterioration of the battery pack in the battery.
3, for each single cell battery alarm condition is judged and recorded.
4, relying on existing environmental monitoring or other power transmission network, to achieve remote monitoring of the battery parameters.
5, check the discharge test, the battery can be timed recording cell voltage and impedance changes, get each single battery discharge curve.
Using E200 Series UPS battery monitoring and management system to protect the security of data center battery

 

E200 Series battery monitoring and management system, its battery and battery packs connected in each single battery parameters in real-time monitoring. Including:

 

1 ) single battery voltage, battery current, and real-time monitoring of ambient temperature ; through optional , can support single battery temperature measurement function


     U400-S battery monitoring system to accurately measure each cell voltage, the battery charge and discharge current , battery voltage , ambient temperature. By extending the temperature monitoring module SUM-TM, system support for monitoring the temperature of the cells and display . Each module supports 24-channel temperature battery temperature acquisition, and remote transmission of data through extensions and 485 . The system automatically detects battery cycle of each single battery voltage, battery current and ambient temperature ; loop detection period of not more than 10 seconds.
 
2 ) has a single battery impedance test capabilities to accurately reflect the state of the battery deterioration


     U400-S battery monitoring system has been testing authority , single battery impedance system test results obtained with the battery deteriorated state should have a high correlation , can be had accurately reflect the deterioration of the battery . Depending on the operating system is able to send commands remotely or locally , automatic battery group for each single battery impedance testing ; single battery impedance testing process, without any human intervention or to make any adjustments to the power state , the system can rely on fully automatically ; under can float , both charge and discharge , offline different states , the battery pack in the monomer impedance testing ; using AC impedance test method , the system should be able to accurately test each single cell impedance , and not the DC resistance . Single battery impedance testing process , no batteries or parts connecting the battery to discharge.
 
3 ) alarm and alarm status output


     Using E200-TP management unit , E200 system can be judged according to the different types of real-time alarm monitoring data , and through communication interface and switch output node for remote transmission of alarm status ;
E200-TP management unit with separate switch output and switch output through various different systems indicate an alarm condition , when the communication connection problem will still be able to judge the state of alarm , and output through the switching node. Depending on the status of the alarm system to provide emergency alarms, warnings and alarms connected to the alarm output switch three categories : emergency alarm ( for the battery circuit , short circuit or high temperature conditions , such as alarm ) ; warning ( for single cell impedance system anomalies alarm ) ; connect alarm ( when problems arise master communication connection between the system and the battery system and so on, through the switch alarm ) .
 
4 ) Communication Interface


     485 communication interface with standard E200-S system , the use of the interface with the U400-TP network management unit with the connection between the E200 system . Meanwhile , U400-TP system can support multiple network interfaces extend way RS232, RS485, RS422, TCP / IP, fiber and so on. Standard system should have a standard 485 or RS422 transmission interface, and supports the standard MODBUS communication protocol . Can be achieved by extending a variety of other interfaces. Support for remote data monitoring and system status queries. Use E200-TP communication interface , can simply achieve interoperability and dynamic environment monitoring network.
 
5 ) local data display and operation


     Except for system data transmission over the network and remote monitoring , the system supports native data show the battery compartment and status queries. By industrial touch screen , you can achieve real-time local data, real-time alarm status display , historical data query, alarm history data inquiry. E200-TP standard 3.5 " industrial touch screen , to achieve local inquiries battery real-time data and historical data under normal circumstances, is a green background ; .. alarm condition , red background touch screen size and appearance options, can be upgraded to 5.7" to 17 " monochrome or color industrial touch screen . upgraded touch screen with battery real-time curve , historical curve display.
 
6 ) Battery connection state detection circuit breakers and contactors :


     E200-TP supports up to eight nodes in a switch input . In addition to monitoring the battery -related status, simply breaker and contactor auxiliary contacts access U400-TP can simultaneously control module and battery related to the state contactors and circuit breakers to be monitored.


We have served many large enterprises (such as China Mobile, Korea KT Telecom, Alibaba Group, Tencent, Baidu), and have a large number of implementation plans and cases of "all kinds of battery monitoring and management". If you need to know, please contact us or send the following request.